- Can be used as dedicated switching device controller or normal RTU with IOs
- Highly reliable control and monitoring of up to three switching devices per ARC600 Status information of three switching devices and three earthing disconnectors
- As RTU can provide 17 Digital Input, 9 Digital Outputs and 2 Analog Inputs
- Integrated wireless communication
- Always on two-way communication based on cellular networks (3G/4G/LTE)
- Communication monitoring and automatic connection re-establishment
- High level data security through internal VPN and Firewall
- Protocol converter
- Conventional IEC-101 and Modbus serial devices can be connected in a reliable way to the modern TCP/IP based IEC-104 and Modbus TCP control systems
- Built-in battery charger with advanced battery control
- Temperature compensated charging
- Battery monitoring/testing (condition monitoring)
- Deep discharge protection
- IEC-101/DNP SCADA compliancy
- IEC 60870-5-101 slave (including dial-up) to support the existing system installations
- Possibility for future SCADA migration from IEC-101 to IEC-104 is supported as the operating mode is selected using the parameter settings
- IEC-101 operation mode as unbalanced slave
- Heater control to limit the effects of ambient temperature variations such as condensation
- Robust aluminium casing design and easy DIN rail mounting
ABB Wireless Controller ARC600
Wireless Controller ARC600 is a compact, solution-based device for remote controlling and monitoring of secondary substations, such as network disconnectors, load break switches and ring main units (RMU) in distribution networks. It enables the SCADA system to wirelessly monitor and control the field devices over the public communication infrastructure (cellular network). Wireless Controller ARC600 utilizes the built-in wireless communication features for reliable and secure end-to-end communication providing remote monitoring and control of three switching devices and can be expanded as required by using external I/O expansion modules.
The operational expenditure can be reduced by lowering the System Average Interruption Duration Index (SAIDI) and System Average Interruption Frequency Index (SAIFI), resulting in lower penalties for undelivered energy. Wireless Controller ARC600 is also ideally suited to be retrofitted to existing applications thus enabling the remote control of these devices and further extending the life cycle of the switching devices itself.
Typically, the IEC-104/DNP-IP protocol is utilized for communication to the SCADA system but for the existing installations with an IEC-101 line or modem and DNP serial, Wireless Controller ARC600 supports the SCADA system.
- Model
- Wireless Controller ARC600
- Categories
- Remote Terminal Unit
- Brand
- ABB
| Description | Value | |
| Dimension | ||
| Height x Width x Depth | 175 x 160 x 108 mm | |
| Weight | 2 kg | |
| Protection class | IP30 | |
| Hardware | ||
| Processor environment | Processor | 32 bit RISC |
| Memory | 128 MB Flash | |
| 128 MB RAM | ||
| Other | Sensor | Temperature |
| Internal clock | Realtime | |
| Power | Power supply | 0~264 Vac or 85~200 Vdc |
| 20~30 Vdc | ||
| Frequency range | 45~65Hz | |
| Input current 100% load 230Vac | 0.8A | |
| Efficiency, typical (230 V AC, 100%load) | >83% | |
| Isolation | Input/ground 1500 V AC RMS 50 Hz 1 min Input | |
| Output 3000 V AC RMS 50 Hz 1 min | ||
| Output/ground 500 V DC | ||
| Power consumption | 10 W typical (when not charging battery), 60 W (full charging) | |
| Casing | Aluminium shell | |
| Approvals | CE | |
| Environment condition | Operation temperature | -30~+55°C (non condensing) |
| Storage temperature | -40~+70°C (storage) | |
| Humidity | 5~85% RH | |
| Supply for external devices | ||
| Output voltage | 21~29 V | |
| Output current | 1 A continuous, 3 A peak | |
| Output overvoltage protection level | 30.5 V | |
| Software | ||
| Network protocol | PPP, IP, ICMP, UDP, TCP, ARP, DNS, DHCP, FTP, TFTP, HTTPS, POP3, SMTP | |
| Tunnelling (VPN) | Open VPN server and client | |
| IPSec | ||
| SSH server and client | ||
| L2TP | ||
| Configuration and management | WEB UI, SSH and serial console | |
| SW remote update | ||
| Arctic Patrol client application for the communication monitoring and management | ||
| Routing and firewall | Static routing, Ethernet over TCP/IP (bridge), Proxy ARP, Port Forward, IP Masquerading/NAT, Firewall | |
| Serial device connectivity | Device server application, Serial data over TCP/IP (such as DNP3 over TCP/IP) | |
| Supported Protocol Conversion | ||
| Master protocol | Slave protocol | |
| IEC 60870-5-104 | IEC 60870-5-101 | |
| IEC 60870-5-104 | Modbus (RTU) profile for Horstmann Compass B | |
| IEC 60870-5-104 | Modbus (RTU) profile for Kries IKI-50 | |
| IEC 60870-5-101 | Modbus (RTU) profile for Horstmann Compass B | |
| IEC 60870-5-101 | Modbus (RTU) profile for Kries IKI-50 | |
| Modbus TCP | Modbus RTU | |
| TCP/IP | Serial gateway – serial port data stream (such as DNP3) | |
| Supported Protocol for IO Controlling | ||
| IEC 60870-5-104 | ||
| IEC 60870-5-101 | ||
| Default I/O Configuration | ||
| Digital inputs (0…60 V DC, >18 V DC detected as 1) | Digital inputs for the disconnector status control | 15 |
| Disconnector 1: Open/ closed, local/remote use, grounding open/closed – 5 pcs | ||
| Disconnector 2: Open/ closed, local/remote use, grounding open/closed – 5 pcs | ||
| Disconnector 3: Open/ closed, local/remote use, grounding open/closed – 5 pcs | ||
| Extra general purpose digital inputs reserved for other use | 2 | |
| Total number of digital inputs | 17 | |
| Digital outputs (1 A/30 V DC continuous carry) | Digital outputs for the disconnector open/close command | 6 |
| Disconnector 1: Open/close – 2 pcs | ||
| Disconnector 2: Open/close – 2 pcs | ||
| Disconnector 3: Open/close – 2 pcs | ||
| Digital output for the load cut (motor overload protection) | 1 | |
| Digital output for the test load of the battery test (test load) | 1 | |
| Digital output for the external heater | 1 | |
| Extra general purpose digital output reserved for other use | 1 | |
| Total number of digital outputs | 10 | |
| Analog inputs (-5…+5 V measurement) | Load measurement (DC motor load current) | 1 |
| Extra reserved for other use | 1 | |
| Total number of analog inputs | 2 | |
| Network Interface | ||
| Ethernet Ports | Ethernet/LAN | 10/100 Base-T. Shielded RJ-45 |
| 1.5 kV isolation transformer | ||
| Ethernet IEEE 802-3, 802-2 | ||
| Serial Ports | Serial 1/Console | Male DB-9 connector |
| IEC 60870-5-101 protocol support | ||
| Full serial and modem signals | ||
| Protection: 15 kV ESD and short circuit | ||
| Console: RS-232, 19200 bps, 8 data bits, 1 stop bit, no parity (8N1) | ||
| Serial 2 | RS-232 DTE, RS-422, RS-485 (selectable) | |
| Male DB-9 connector | ||
| IEC 60870-5-101 protocol support | ||
| Full serial and modem signals | ||
| Protection: 15 kV ESD and short circuit | ||
| Wireless network interfaces (WAN) | ||
| 3G | GPRS/EDGE | 1900/1800/900/850 MHz |
| WCDMA/HSPA+ | 2100/1900/900/850 MHz | |
| 4G/LTE | GPRS/EDGE | 1900/1800/900/850 MHz |
| WCDMA/HSPA+ | 2100/1900/900/850 MHz | |
| LTE | 2600 (band 7)/2100 (band 1)/1800 (band 3)/900 (band 8)/800 (band 20) MHz | |
| Electromagnetic compatibility tests | ||
| Emission tests according to the test specification IEC 61850-3 (Edition 2.0 2013-12) | Radiated disturbance | CISPR 16-2-3 |
| Conducted disturbance | CISPR 16-2-1 | |
| Immunity tests according to the test specification IEC 61850-3 (Edition 2.0 2013-12) | Electrostatic discharge (ESD) | EN 61000-4-2 (2008-12) |
| Radiated radio frequency electromagnetic field | EN 61000-4-3 (2006-02) | |
| Electrical fast transient (EFT) | EN 61000-4-4 (2012-04) | |
| Surge | EN 61000-4-5 (2005-11) | |
| Conducted radiofrequency electromagnetic field | EN 61000-4-6 (2008-10) | |
| Power frequency magnetic field | EN 61000-4-8 (2009-09) | |
| Voltage dips | EN 61000-4-11 (2004-03) | |
- Electric Switching Controller
- Electric Distribution Controller
- Key point & Recloser controller
- General Remote Terminal Unit