Non Modular Rectifier
product

Non Modular Rectifier

Non-Modular Rack Mounted Rectifier is an embedded and software configurable battery charger system that is suitable for small to medium battery banks that can provide up to 2400Watt (on 48Vdc output).

The system is provided with a processor-based power module with 3-rows LCD display to monitor and configure system setting. Single output can be chosen from the available range which is 24VDC (up to 70A), 48Vdc (up to 50A) and 110Vdc (up to 20A). The input has a wide range voltage from 180Vac to 300Vac auto adjust. The system is provided with configurable software with buttons, so need any other tools to configure and test.

This DC charger system is suitable for most industrial applications equipment that require batteries as power backup in event main line if failed such as SCADA System, Communication system, Power backup system, etc.

Model
Categories
DC Supply
Brand
SIP-BC
  • Types of output 24Vdc/48Vdc/110Vdc 
  • Wide range of Input Voltage 
  • Software configurable to set operating and alarm value 
  • Microprocessor based in power module 
  • LCD display for monitor and configuration
  • 2 step charging with temperature compensation
  • Battery automatically on line to support load anytime AC fails
  • Low voltage disconnect protects battery from total discharge
  • Alarm contacts: AC fail, Comms fail, Battery status
  • Modbus data digital output
ITEM DESCRIPTION REMARK
Model 24VDC 48VDC 110VDC
Input Properties
Voltage Input 180-300 Vac Auto adjust
Frequency Input 45~55 + 5% Auto adjust
Power factor >0.99
Efficiency >0.96%
Output Properties
Voltage Output (Vdc) 20Vdc~36Vdc 42Vdc~59Vdc 90Vdc~129Vdc Configurable range value
Max. Current Output 70A 50A 20A Configurable max value
Voltage Regulation Precision ≤0.6%
Load Regulation ≤0.5%
Voltage Regulation ≤0.1%
Peak noise voltage ≤200mV ; 0~20MHz
Psophometric noise voltage ≤ 2mV
Wide frequency noise voltage ≤50mV : 3.4kHz ~ 150kHz
≤20mV : 0.15 MHz 30MHz
Discrete noise voltage ≤5mV : 3.4kHz ~ 150kHz
≤3mV : 150kHz ~ 200kHz
≤2mV : 200kHz ~ 500kHz
≤1mV : 0.5MHz ~ 30MHz
Current Limiting 0~110% rated current Configurable value
Equalized-current imbalance ≤3%
Charging Mode Float/Equalizing Configurable value
Display 3-row LCD backlight
Software configuration Set operating and alarm value with buttons setting
Data communication RS232 with Modbus (default) or SNMP (optional)
Alarms & Protections
1. Over-current protection
Over-current protection of input Fuse
Over-current protection of output Fuse
Over-current protection of PFC Diverter
Short circuit protection Reduce input current to protect
2. Over-voltage & low-voltage protection
Input low-voltage protection 80±5V, hysteresis:10V ~ 20V Configurable value
Input over-voltage protection 300±5V,hysteresis:5 ~ 20V Configurable value
Output over-voltage protection 59 ±1V Configurable value
Over- temperature protection default value 80℃, hysteresis:10℃ Configurable value
3. Battery Protection
Output battery protection Use Low Voltage Detection Relay Configurable value
4. Dry-Contact
Type of contact 3 dry contact outputs
Type of alarm Contact 1: Main failure, LVD failure, Over-voltage input, Fan Failure
Contact 2: Battery fuse trip
Contact 3: Over-temperature and communication failure
5. Alarm Sounds Audible beeping sound & multicolour LED indicator
Panel size 19-inch Rack Mounted

88mm(H)×500mm(W)×450mm(D)

  • Telecom base stations
  • Power stations
  • Protection equipment
  • CCTV
  • Industrial automation
  • SCADA/PLC and other control system